Control Zones
For heating, ventilation and air-conditioning distribution and control purposes, the boat is divided into the zones in the next table. With a K=1, Sharina requires approx. 37,810 BTU/h of heating. The main diesel furnace supplies this, sufficient for the coldest weather.
 
HVAC Zones
Description Zone Distribution Air
Conditioning
BTU (K=1) Heating
BTU(K=1)
Forward cabin 1 44% 24,349 16,637
Aft cabin 2 17% 9,408 6,428
Pilothouse 3 18% 9.961 6,806
Salon 4 21% 11,621 7,940
Engine room 5 - - ?
 
 
But what happens in an emergency? In the event the furnace fails, the Bristol Pacific model diesel stove in the galley can provide 6,500-16,250 BTU to heat the forward accommodation. At the lower heat setting it could maintain a temperature differential of 21 C, while the higher one maintains Sharina’s design differential requirement of 55 C in the forward compartment.